| Installer Setup |
| Choices |
Number |
(press Time Uparrow key to change)
|
| Fan operation. |
2 |
- 0=Conventional applications where equipment controls fan operation in heat mode.
- 1=Heat pump or electric heat applications where thermostat controls fan operation in heat mode.
|
Heating cycle rate cph=cycles per hour |
4 |
- 1=1 cph used for radiant floor heat, gravity system
- 3=3 cph used for hot water systems or high efficiency furnaces
- 6=6 cph (default) used for conventional heat
- 9=9 cph used for electric heat systems
|
| System setting adjustment |
12 |
- 0=Auto changeover
- 1=Manual changeover (default)
- 2=Fixed auto changeover
|
| Adaptive Intelligent Recovery (trademark) control |
13 |
- 0=Adaptive Intelligent Recovery control is
activated (system starts early so setpoint is reached by start of program period)
- 1=Conventional recovery (system starts recovery at
programmed time)
|
| Degree temperature display |
14 |
- 0=Temperature is displayed in °F
- 1=Temperature is displayed in °C
|
| Clock format |
16 |
12-hour clock format
24-hour clock format |
| Extended fan operation in heating* |
19 |
- 0=No extended fan operation after the call
for heat ends
- 1=Fan operation is extended 90 seconds after the call for heat ends
|
| Extended fan operation in cooling* |
20 |
- 0=No extended fan operation after the call for cool ends
- 1=Fan operation is extended 90 seconds after the call for cool ends.
|
| Outdoor temperature display (select models) |
24 |
- 0=No outdoor temperature is displayed
- 1=Outdoor temperature is displayed. Needs a C7089B1000 Outdoor Sensor to operate
|
| Deadband |
30 |
- Heating and cooling setpoints can be set no closer than the chosen value:
- 2=2°F (1°C) apart
- 3=3°F (1.5°C) apart (default)
- 4=4°F (2°C) apart
- 5=5°F (2.5°C) apart
- 6=6°F (3°C) apart
- 7=7°F (3.5°C) apart
- 8=8°F (4°C) apart
- 9=9°F (4.5°C) apart
- 10=10°F (5°C) apart
|
| Minimum off time for the compressor |
33 |
0 thur 5=Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor (5 is the default).
|
| Temperature range stops in heating |
34 |
40 to 90=Temperature range (1°F increments) heating setpoint can be set to (90 is the default) |
| Temperature range stops in cooling |
35 |
45 to 99=Temperature range (1°F increments) cooling setpoint can be set to (45 is the default). |
| Temperature display adjustment |
37 |
- 0=No difference in displayed temperature and actual room temperature (default)
- 1=Display adjusts to 1°F higher than actual room temperature
- 2=Display adjusts to 2°F higher than actual room temperature
- 3=Display adjusts to 3°F higher than actual room temperature
- 4=Display adjusts to 1°F lower than actual room temperature
- 5=Display adjusts to 2°F lower than actual room temperature
- 6=Display adjusts to 3°F lower than actual room temperature
|